D. Alarm output
The system can be configured to operate one of the following outputs
provided on the controller:
Onboard buzzer - emits a continuous tone
Pillar / Courtesy Light contact (potential-free normally-open contact,
fuse-protected - 5A)
Aux IO (this is an open collector drive, maximum current draw 3A, not
fuse-protected)
Safety beam common (this is an open collector drive, maximum current
draw 3A, not fuse-protected)
Status LED output (operate up to three LEDs in parallel or interface with
the CP78 MULTI-LED driver card)
Menu 7 - Pedestrian Opening
This feature is associated with the PED input on the controller. When activating
this input, the system will open the gate to the Pedestrian Open position, and
then automatically close after the Pedestrian Autoclose time lapses. If the PED
connection to Com is maintained, then the gate will remain open, and when the
connection is broken, it will close after the Pedestrian Autoclose time has
expired.
The time taken for the gate to open to pedestrian is dependent on the pedestrian
Pre-open Delay and the time required for the gate to close from the pedestrian
position is dependent on the Pedestrian Pre-close Delay.
The Warning Light is any light wired to the Pillar Light contacts, as
described in Menu 9.
1. Pedestrian Open Position
Sets the maximum opening of the pedestrian gate in metres, in one
centimetre steps.
2. Pedestrian Autoclose Time
Sets the Autoclose time in seconds after a Pedestrian Opening. This time can
be set from zero seconds to four minutes in one second steps.
3. Pedestrian Pre-open Delay
Sets the time delay between the pedestrian input being activated, and the
gate actually opening. This enhances safety in cases where the pedestrian
has to reach through the gate in order to activate the pedestrian input.
A Warning Light would typically be active during this delay. This delay can be
set from zero seconds to four minutes in one second steps.
4. Pedestrian Pre-close Delay
Sets the time delay between the Pedestrian Autoclose timer expiring, and the
gate actually closing. A Warning Light would typically be active during this
delay. This delay can be set from zero seconds to four minutes in one second
steps.